Programming Mettler Toledo Scale PCB 30356386 BCA-223-150X-119A-100

Serial settings of 9600/8/none/1 with Proto U and the continuous output enabled in Send WT.

  1. Connect Mettler Toledo programming display.
    (We use the Mettler Toledo BC60 Series Graphical Replacement Display 0271-1100-000)
  2. Press & Hold up arrow.
  3. Press Setup
  4. Press COMM
  5. Select "Serial"
  • Baud: 9600
  • DatBit: 8
  • Parity: none
  • Stop: 1
  • Protoc: Proto U
  1. Go back to COMM
  • SendWT: Contin (0.2s)
  1. Go back to Home

  2. Select End and then select Save.

If you have any questions or need assistance, please contact us at 509-473-0252 or info@innovate.ag